This post describes the standards and manual calculations for sizing batteries used in UPS.
Let us have total load of 16 kW with 0.8 pf, which needs to be supported by battery backup for at least 1 hr, when the grid fails. Before choosing the battery with respect to cost or brand, there are many questions to be answered
Battery sizing calculation differs with respect to the application as well
The battery load of UPS should be calculated by considering the following 4 margin factors as shown below
Actual load / Inverter Efficiency = Nominal battery load
Temperature correction factor x Design Margin x Aging Margin x Overloading factor = Battery load
Selected Battery type Sealed Maintenance Free VRLA.
UPS Output rating = 20 kVA
Output Power Factor = 0.8
Actual Load = 16 kW
Inverter Efficiency (EFF) = 94%
Nominal Battery load = 17.02 kW